Fuse Sizes
Distribution fuse and circuit breaker size marking is included in the manual to indicate that the
unit shall be connected with a Listed Cartridge Nonrenewable fuse or Inverse time circuit beraker,
rated 600 Vac with the current ratings as shown in the table below or Type E Combination Motor
Controller marking is included in the manual to indicate that the unit shall be connected with,LS
Industrial System Co.,Ltd,Type E Combination Motor Controller MMS Series with the ratings as
shown in the table below:
Inverter Model
WJ200-001S
WJ200-002S
WJ200-004S
WJ200-007S
WJ200-015S
WJ200-022S
WJ200-001L
WJ200-002L
WJ200-004L
WJ200-007L
WJ200-015L
WJ200-022L
WJ200-037L
WJ200-055L
WJ200-075L
WJ200-110L
WJ200-150L
WJ200-004H
WJ200-007H
WJ200-015H
WJ200-022H
WJ200-030H
WJ200-040H
WJ200-055H
WJ200-075H
WJ200-110H
WJ200-150H
Fuse
Rating
Type
(Maximum A)
10A, AIC 200kA
20A, AIC 200kA
30A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
20A, AIC 200kA
Class J,
30A, AIC 200kA
Class CC,
Class G,
60A, AIC 200kA
Class T
80A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
30A, AIC 200kA
50A, AIC 200kA
Inverse Time
Circuit Breaker
Rating
(Maximum A)
30A
30A
100A
20A
40A
3
Type E CMC
MMS-32H,
240V,40A
MMS-32H,
240V,40A
or
MMS-63H,
240V,54A
MMS-100H,
240V,80A
MMS-32H,
480V,40A
or
MMS-63H,
480V,52A

Advertisement