F u n c .
N a m e
C o d e
C071
Communication speed
C072
Modbus address
Communication parity
C074
Communication stop bit
C075
C076
Communication error
select
C077
Communication error
time-out
C078
Communication wait time
O input span calibration
C081
C082
OI input span calibration
C085
Thermistor input (PTC)
span calibration
C091
Debug mode enable
Communication selection
C096
C098
EzCOM start adr. of master
C099
EzCOM end adr. of master
C100
EzCOM starting trigger
" C " F u n c t i o n
D e s c r i p t i o n
Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
00No parity
01Even parity
02Odd parity
Two option codes:
11 bit
22 bit
Selects inverter response to
communications error.
Five options:
00Trip
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerates to a stop
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 s.
0.0 = disabled
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms.
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor between the external
frequency command on terminals
L–OI (currnt input) and the
frequency output,
range is 0.0 to 200%
Scale factor of PTC input.
Range is 0.0 to 200%
Factory use only.
Do not change.
00Modbus-RTU
01 EzCOM
02 EzCOM<administrator>
1. to 8.
1. to 8.
00 Input terminal
01 Always
71
D e f a u l ts
Run
Mode
I n i t i a l
Edit
d a ta
*
1
05
*
1
1.
*
1
00
*
1
1
*
1
02
*
1
0.00
*
1
0.
100.0
100.0
100.0
00
1.
1.
00
U n i ts
baud
bit
s
ms
%
%
%