Chapter 3 Overview
User settings (continued)
Submenu
On/Off settings
Energy saving
(continued)
Sleep mode
Remote command
Bypass standby
Battery settings Automatic battery test
Low battery warning
20
Available settings
[Disabled] [100W] ... [1000W]
If Enabled, UPS will shut down after 5
minutes of back-up time, if load is less
than threshold.
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS is
OFF.
If Enabled, LCD and communication
stays ON 90 minutes after UPS is OFF.
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode:
[No test] [Every ABM cycle]
[0%] ... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Default settings
[Disabled]
[Enabled]
[Enabled]
[Enabled] for 3:1
(8PX and 9PX)
models
[Disabled] for 1:1
(8KX and 9KX)
models
[Every ABM cycle]
[20%]