GE AF-600 FP Design Manual page 35

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

1. Start/Stop via switch connected between terminals 12 (+24 V) and 18.
2. Temperature reference via a potentiometer (-5 to +35°C, 0 10 V) connected
to terminals 50 (+10 V), 53 (input) and 55 (common).
3. Temperature feedback via transmitter (-10-40°C, 4-20 mA) connected to
2
terminal 54. Switch S202 behind the keypad set to ON (current input).
2.8.9 Programming Order
Function
1) Make sure the motor runs properly. Do the following:
Set the motor parameters using nameplate data.
Run Auto Tune.
2) Check that the motor is running in the right direction.
Run Motor Rotation Check.
3) Make sure the frequency converter limits are set to safe values
Check that the ramp settings are within capabilities of the drive
and allowed application operating specifications.
Prohibit the motor from reversing (if necessary)
Set acceptable limits for the motor speed.
Switch from open loop to closed loop.
4) Configure the feedback to the PID controller.
Select the appropriate reference/feedback unit.
5) Configure the set-point reference for the PID controller.
Set acceptable limits for the set-point reference.
Choose current or voltage by switches S201 / S202
6) Scale the analog inputs used for set-point reference and feedback.
Scale Analog Input 53 for the pressure range of the potentiom-
eter (0 - 10 Bar, 0 - 10 V).
Scale Analog Input 54 for pressure sensor (0 - 10 Bar, 4 - 20 mA) AN-22
7) Tune the PID controller parameters.
Adjust the drive's Closed Loop Controller, if needed.
8) Finished!
Save the parameter setting to the keypad for safe keeping
34
Par. no.
Setting
P-0# & F-04, F-05
As specified by motor name plate
P-04
Enable complete Auto Tune [1] and then run the Auto Tune
function.
P-08
If the motor runs in the wrong direction, remove power tem-
porarily and reverse two of the motor phases.
F-07
60 sec.
F-08
60 sec.
Depends on motor/load size!
Also active in Hand mode.
H-08
Clockwise [0]
F-16
10 Hz, Motor min speed
F-15
50 Hz, Motor max speed
F-03
50 Hz, Drive max output frequency
H-40
Closed Loop [3]
CL-12
Bar [71]
CL-13
0 Bar
CL-14
10 Bar
AN-10
0 V
AN-11
10 V (default)
AN-14
0 Bar
AN-15
10 Bar
4 mA
AN-23
20 mA (default)
AN-24
0 Bar
AN-25
10 Bar
CL-93
See Optimization of the PID Controller, below.
CL-94
K-50
All to keypad [1]
AF-600 FP Design Guide