GE AF-600 FP Design Manual page 167

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

515
Application Orientated Control cannot recognize the EE-
PROM data
516
Cannot write to the EEPROM because a write command
is on progress
517
Write command is under time out
518
Failure in the EEPROM
519
Missing or invalid Barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-1279 A can-telegram that has to be sent, couldn't be sent
1281
Digital Signal Processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read Digital Signal Processor software version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1317
Option SW in slot C0 is not supported (not allowed)
1318
Option SW in slot C1 is not supported (not allowed)
1379
Option A did not respond when calculating Platform Ver-
sion.
1380
Option B did not respond when calculating Platform Ver-
sion.
1381
Option C0 did not respond when calculating Platform Ver-
sion.
1382
Option C1 did not respond when calculating Platform Ver-
7
sion.
1536
An exception in the Application Orientated Control is reg-
istered. Debug information written in keypad
1792
DSP watchdog is active. Debugging of power t data Motor
Orientated Control data not transferred correctly
2049
Power data restarted
2064-2072 H081x: option in slot x has restarted
2080-2088 H082x: option in slot x has issued a powerup-wait
2096-2104 H083x: option in slot x has issued a legal powerup-wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
Power card configuration is determined to be incorrect at
power up
2330
Power size information between the power cards does not
match
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state running)
2816
Stack overflow Control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
keypad Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-5122 Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with Control
board hardware
5124
Option in slot B: Hardware incompatible with Control
board hardware
5125
Option in slot C0: Hardware incompatible with Control
board hardware
5126
Option in slot C1: Hardware incompatible with Control
board hardware
5376-6231 Out of memory
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card.
The problem could be on the power card, on the gate drive card, or the ribbon
cable between the power card and gate drive card.
WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove short-circuit connection.
Check par. E-00 Digital I/O Mode and par. E-51 Terminal 27 Mode.
166
WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove short-circuit connection.
Check par. E-00 Digital I/O Mode and par. E-52 Terminal 29 Mode.
WARNING 42, Overload of Digital Output on X30/6 or Overload of Digital
Output on X30/7
For X30/6, check the load connected to X30/6 or remove short-circuit con-
nection. Check . E-56 X30/6 Digital Out (OPCGPIO).
For X30/7, check the load connected to X30/7 or remove short-circuit con-
nection. Check . E-57 Term X30/7 Digital Out (OPCGPIO).
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch mode power supply
(SMPS) on the power card: 24 V, 5V, +/- 18V. When powered with 24 VDC with
the OPC24VPS option, only the 24 V and 5 V supplies are monitored. When
powered with three phase mains voltage, all three supplied are monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external V DC backup power
supply may be overloaded, otherwise contact your GE supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of allowable limits.
The power supply is measured on the control card.
WARNING 49, Speed limit
When the speed is not within the specified range in par. F-18 and par. F-17.
the drive will show a warning. When the speed is below the specified limit in
par. H-36 Trip Speed Low [RPM] (except when starting or stopping) the drive
will trip.
ALARM 50, Auto tune calibration failed
Contact your GE supplier.
ALARM 51, Auto tune check Unom and Inom
The setting of motor voltage, motor current, and motor power is presumably
wrong. Check the settings.
ALARM 52, Auto tune low Inom
The motor current is too low. Check the settings.
ALARM 53, Auto tune motor too big
The motor is too big for the Auto tune to be carried out.
ALARM 54, Auto tune motor too small
The motor is too big for the Auto tune to be carried out.
ALARM 55, Auto tune Parameter out of range
The parameter values found from the motor are outside acceptable range.
ALARM 56, Auto tune interrupted by user
The Auto tune has been interrupted by the user.
ALARM 57, Auto tune timeout
Try to start the Auto tune again a number of times, until the Auto tune is carried
out. Please note that repeated runs may heat the motor to a level where the
resistance Rs and Rr are increased. In most cases, however, this is not critical.
ALARM 58, Auto tune internal fault
Contact your GE supplier.
WARNING 59, Current limit
The current is higher than the value in par. F-43 Current Limit.
AF-600 FP Design Guide

Advertisement

Table of Contents
loading

Table of Contents