Mains Supply 3 x 380 - 480 VAC
Typical Shaft output at 400 V
[kW]
Typical Shaft output at 460 V
[HP]
Unit Size IP21
Unit SizeIP54
Unit Size IP00
Output current
Continuous
(at 400 V) [A]
Intermittent (60 sec over-
load)
(at 400 V) [A]
Continuous
(at 460 V) [A]
Intermittent (60 sec over-
load)
(at 460 V) [A]
Continuous KVA
(at 400 V) [KVA]
Continuous KVA
(at 460 V) [KVA]
Max. input current
Continuous
(at 400 V ) [A]
Continuous
(at 460 V) [A]
Max. cable size, mains, mo-
tor and load share [mm
(AWG
2)
)]
Max. external pre-fuses [A]
Estimated power loss
at rated max. load [W]
Weight,
Unit Size IP21, IP 54 [kg]
Weight,
Unit Size IP00 [kg]
Efficiency
4)
Output frequency
Heatsink overtemp. trip
Power card ambient trip
315
450
51
51
52
600
660
540
594
416
430
590
531
4x240
2
(4x500 mcm)
(4x500 mcm)
1
700
7630
4)
263
221
AF-600 FP Design Guide
355
400
500
600
51
51
51
51
52
52
658
745
724
820
590
678
649
746
456
516
470
540
647
733
580
667
4x240
4x240
(4x500 mcm)
900
900
7701
8879
270
272
234
236
0.98
0 - 600 Hz
95 °C
68 °C
450
600
51
51
52
800
880
730
803
554
582
787
7
718
4x240
(4x500 mcm)
900
9428
313
277
139