GE AF-600 FP Design Manual page 149

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Surroundings:
Unit Size 1x types
Unit Size 21 and 22 types
Unit Size 23 and 24 types
Unit Size 31 and 32 types
Unit Size 33 and 34 types
Unit Size 41, 42, and 51 types
Unit Size 43, 44, and 52 types
Unit Size 61/63
Unit Size 62/64
IP21/Nema 1 kit for all unit sizes 1x, 2x, and 3x
Vibration test unit size 1x, 2x, 3x
Vibration test unit size 4x, 5x, 6x
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
- with full output power of typical EFF2 motors (up to 90% output current)
7
- at full continuous Drive output current
1)
For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions
EMC standards, Emission
EMC standards, Immunity
See section on special conditions!
Control card performance:
Scan interval
Control card, USB serial communication:
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB connector on
frequency converter or an isolated USB cable/converter.
Protection and Features:
Electronic thermal overload motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95 °C ± 5°C. An overload temperature
cannot be reset until the temperature of the heatsink is below 70 °C ± 5°C (Guideline - these temperatures may vary for different power sizes, enclosures
etc.). The frequency converter has an auto derating function to avoid it's heatsink reaching 95 deg C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
148
S test
2
IP 20/Chassis, IP 21kit/Type 1, IP55/Type12
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
AF-600 FP Design Guide
IP55/Type12
IP20/Chassis
IP55/Type 12
IP20/Chassis
IP21/Type 1, IP54/Type12
IP00/Chassis
IP21, 54/Type1, 12
IP21, 54/Type1, 12
IP21/NEMA 1/on top of enclosure
1.0 g
0.7 g
class Kd
max. 50° C
1)
max. 50 ° C
1)
max. 45 ° C
1)
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
3000 m
EN 61800-3, EN 61000-6-1/2,
: 5 ms
1.1 (Full speed)
USB type B "device" plug