Huawei NetCol5000-A050 User Manual page 94

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Step 4 Install the drainpipe. Rigid pipe connection (A) and hose connection (B) are
supported. Select a connection mode based on site requirements.
● The external drainpipe must have a downward gradient (> 1:100) along the
drainage direction, and no accumulated water is allowed.
● The maximum lift of the drainage pump is 4 m, with the drainage height and
drainpipe system resistance considered. If the total system lift is greater than 4
m, the water pump flow will be less than the rated flow. In this case, shorten
the drainpipe length, reduce the number of bends (to reduce local resistance),
or decrease the drainage height to ensure that the total system lift is less than
or equal to 4 m.
Total lift of the water pump = Drainage height (Vertical height difference
between the water pump and the highest point of the drainpipe) + Drainpipe
system resistance (Length of the straight drainpipe section x Equivalent lift of
the straight drainpipe section + Number of bends x Equivalent lift of bends)
Select a DN20 (3/4 inch) drainpipe. The equivalent lift of each meter of the
straight drainpipe section is 0.0323 m, and the equivalent lift of each bend is
0.0317 m.
Assume that the drainage height is 3.9 m, the straight drainpipe section is 5 m,
and two bends are used. The total lift of the water pump is 4.129 m.
Calculation formula: 3.9 m + 5 x 0.0323 m + 2 x 0.0317 m = 4.129 m In this
case, the total lift is greater than 4 m, and the water pump flow is less than the
rated flow. It is necessary to shorten the drainpipe length, reduce the number
of bends (to reduce local resistance), or decrease the drainage height.
● The drainpipe (including the connectors) must be wrapped with thermal
insulation foam.
Issue 04 (2022-12-15)
Figure 4-47 Welding pipes
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
84

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a050h4we2Netcol5000- a050h40e2

Table of Contents