Huawei NetCol5000-A050 User Manual page 121

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Tab
System
Settings
Issue 04 (2022-12-15)
Parameter
Cold aisle
temperature and
humidity sharing
Hot aisle temperature
and humidity sharing
Low temperature
component
Outdoor unit
condensate mode
Temp control
intelligent monitoring
board
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
This function can be enabled only
when at least one smart cooling
product in the teamwork group is
equipped with cold aisle T/H sensors. If
this function is enabled, the master
unit in the teamwork group collects
the cold aisle temperature and
humidity values from all units
equipped with cold aisle sensors, and
synchronizes the temperature and
humidity control type and setpoints to
all slave units.
This function can be enabled only
when at least one smart cooling
product in the group is equipped with
hot aisle T/H sensors. If this function is
enabled, the master unit in the
teamwork group collects the hot aisle
temperature and humidity values from
all units equipped with hot aisle
sensors, and synchronizes the
temperature and humidity control type
and setpoints to all slave units.
Specifies whether a low temperature
component is used.
● Air-cooled: The outdoor unit is an
air-cooled outdoor unit.
● Water-cooled: The outdoor unit is a
water-cooled module.
A temperature control intelligent
monitoring board is used to monitor
the outdoor environment.
Check the interior of the electric
control box of the outdoor unit:
● If there is an intelligent
temperature control monitoring
board, set this parameter to Yes.
● If there is no intelligent
temperature control monitoring
board, set this parameter to No.