NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Figure 4-33 Securing the low temperature component
----End
4.7 Installing Pipes
4.7.1 Top Pipe Routing
Step 1 Exhaust nitrogen from needle valves in sequence.
1.
2.
3.
Step 2 Determine the pipe route.
Issue 04 (2022-12-15)
Connect the rubber hose of the pressure gauge to the corresponding needle
valve.
When the pressure gauge valve is opened, there is a loud sound of airflow at
the beginning, and then the airflow gradually disappears.
After the airflow noise disappears, remove the rubber hose and install the
valve bonnet.
Figure 4-34 Exhausting nitrogen
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
77