Huawei NetCol5000-A050 User Manual page 141

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
3.
4.
Step 5 Tap the text box next to SNMP Port, set SNMP Port based on the actual port
number, and tap Submit.
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
3.
4.
----End
Issue 04 (2022-12-15)
MD5 and DES protocols are not secure. It is recommended that you set Auth
Protocol to SHA2-512, and set Prop Protocol to AES-256. The following
operations use the recommended settings as an example.
Figure 6-16 Setting the protocol type
NO TICE
Passwords of an authentication protocol and proprietary protocol must
comply with the following policies:
– The password must contain at least two types of characters among
uppercase letters (A–Z), lowercase letters (a–z), and digits (0–9). The
password must contain 8 to 15 characters and be different from the user
name or its reverse.
– A password must not be a string containing duplicate sections, such as
12a12a12a.
– Weak passwords such as Password, Admin_1243, and Changeme_123 are
not allowed.
Set SHA Password and Confirm Password as planned.
Set AES Password and Confirm Password as planned.
NO TE
SNMP Port is set to 161 by default.
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
NO TE
Trap Port is set to null by default.
Select SNMP Version. If an SNMPv3 user is configured, it is recommended
that SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, you need to select SNMPv3 User Name.
For other protocols, you need to set Trap Community.