NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
Settings screen, as shown in
Figure 5-4 Teamwork settings
Step 2 Set teamwork parameters.
All teamwork parameters can be set on the master smart cooling product. Only
Teamwork group No., System address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling
products. Other parameters of the slave units will be modified by the master unit
synchronously.
Table 5-7 Teamwork Settings
Parameter
Teamwork group num
System address
Enable teamwork CAN
resistor
Issue 06 (2022-12-15)
Table 5-7
describes how to set the parameters.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Figure
5-4.
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned unit address. The addresses of
units in the same teamwork group must be unique.
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
5 Power-On Commissioning