Step 1 Secure the micro differential pressure sensor and sheet metal to the cabinet using
M5 tapping screws.
Figure 4-76 Securing a differential pressure sensor (NetCol5000-C065)
Figure 4-77 Securing a differential pressure sensor (NetCol5000-C030/C032)
Step 2 Connect the pressure inlet tube.
Issue 06 (2022-12-15)
Cold aisle containment: Connect a pressure inlet tube to the + mark and route
it to the aisle through the hole on the top of the cabinet. Ensure that the
pressure inlet faces downwards. Connect another pressure inlet tube to the –
mark and route it to the cabinet top through the hole atop.
Hot aisle containment: Connect a pressure inlet tube to the + mark and route
it to the cabinet top through the hole atop. Connect another pressure inlet