11.5.11 Application - 1-button operating mode "Adjust RTC"

The operating mode of linked room temperature controllers can be switched over via the
application with a press of the button.
The following communication objects are available:
"Sx: enable"
"Sx: comfort operating mode"
"Sx: Eco operating mode"
"Sx: frost operating mode"
Object type "1-bit" serves for activating room temperature controllers that have the 1-bit objects
for the switchover of the operating modes.
Object type "1 byte" serves for activating room temperature controllers that have a 1-byte object
for the switchover of the KNX operating modes.
The following operating modes and object values can be set via the application:
Auto (value "0")
Comfort (value "1")
Standby (value "2")
Eco (value "3")
Frost protection, heat protection (value "4")
The function can be temporarily blocked via 1-bit object "Sx: enable".
In each case, the application makes a separate set of parameters and communication objects
available in function block x for both buttons. The second button of each function block can be
occupied with an additional button function.
Note
The parameters for application "1-button operating mode "Adjust RTC"" can be
called up via general parameters and extended parameters.
Note
The number (S1 - Sx) of the object depends on the function block and the button
number.