Climatic ambient conditions
The S7-1500 automation system may be used in the following climatic ambient conditions:
Table 16- 9
Climatic ambient conditions
Ambient conditions
Temperature:
horizontal mounting
position:
vertical mounting position:
Temperature variation
Relative humidity
Barometric pressure
Concentration of pollutants
S7-1500 Automation System
System Manual, 02/2014, A5E03461182-AB
Permissible range
0 °C to 60 °C
0 °C to 40 °C
10 K/h
from 10 % to 95 %
from 1080 hPa to 795 hPa
SO
: <0.5 ppm;
2
RH <60%, no condensation
H
S: < 0.1 ppm;
2
RH < 60 %, no condensation
ISA-S71.04 severity level G1; G2; G3
16.4 Mechanical and climatic ambient conditions
Comments
To increase the service life of the display, the
display switches off when the permitted
operating temperature is exceeded.
Further information about the temperatures
at which the display switches off and back on
again is available in the technical data of the
manuals of the CPUs.
-
Without condensation, corresponds to
relative humidity (RH) class 2 in accordance
with IEC 61131 part 2
corresponds to an altitude of -1000 m to
2000 m
-
-
Technical specifications
191