Fault information and trouble shooting
Trip
Trip Type
code
ECE
Encoder fault
Fast current limit
LC
fault
Terminal
EF2
fault
PIDE
PID feedback error 1. PID feedback offline
Overload
OLP2
alarm error
SINAMICS V50 converter
73
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Possible causes
1. Encoder signal wires
are connected
reversely.
2. Encoder signal wires
get damaged.
3. Encoder damaged.
4. Dual-way encoder
detected motor
direction is not match
with drive direction.
1. Load too large or
motor blocked to stall
2. Drive power rating
too small
3. Drive output circuit
loop grounded or SC.
1. The FWD or REV
terminals close and get
close
power on. But drive is
set to not allow the
restart after power
failure recovery.
1. Frequency drive
pre-
output current is
higher than set pre-
alarm threshold
Solutions
1. Check whether the
encoder signal is correctly
connected.
2. Check whether the
encoder wiring is broke.
3. Change the encoder.
4. Change the encoder
direction (F3.16) or alter
motor wiring sequence.
1. Decrease the load and
check motor and mechanical
part status
2. Choose higher power
drive
3. Remove the external fault
1. Disconnect the FWD or
REV terminal first and then
power on the drive.
2. Close the fault detection
function for closed terminal
fault (FC.11=0)
1. Check PID feedback line.
2. Disable PID feedback
detection (F8.24=0.0%)
3. Increase PID feedback
offline detection time
(F8.25)
1. Disable pre-alarm
function(FC.19=0)
2. Increase pre-alarm
threshold value (FC.02) 3.
3. Increase pre-alarm
detection time(FC.03)