Siemens 6SN1123-1AA00-0DA2 Configuration Manual page 157

Simodrive 611 series drive converter
Table of Contents

Advertisement

6 Infeed Modules
6.2 Interface overview
Terminals L1, L2
Terminal R
6-156
External switching voltage for the coil circuit of the line contactor
Is used to supply the coil circuit of the internal line contactor only at the 80 kW
and 120 kW I/R modules (do not connect between the I/R module and reactor).
≥ 4 A, version gL
Fuse: I
r
2–ph. 360 to 457 V AC/45 to 53 Hz; 400 to 510 V/57 to 65 Hz
Table 6-4
Technical data of the internal line and pre–charging contactor
I/RF module
6SN114j–1BB0j–0EA1
6SN114j–1BB0j–0FA1
Matching transformer for the coil connections L1, L2 at the line supply voltage 230 V and
380 V; for two 5TK5022–0AR0 contactors.
Table 6-5
Matching transformer SIDAC 1–phase autotransformer
Type
Throughput rating [VA]
Input voltage [V]
Output voltage [V]
Output current [A]
Insulating material class
Applicable standard
Frequency [Hz]
Vector group
Degree of protection
Dimension sketch
for voltage fluctuations
Note
If, for the 80/104 kW or 120/156 kW I/R module, the line supply voltage at
terminals L1, L2 fails or fuses F1, F2 trip, then only the pulses in the I/R module
are cancelled and the internal line contactor drops–out.
This is displayed using the "line fault" LED, the ready relay and also the
contactor signaling contacts. In this case, in order to re–close the internal line
contactor, terminal 48 must be inhibited (de–energized) and re–energized after
≥one second or the unit must be powered–down/powered–up.
Reset
The fault signal is reset using a pushbutton (pulse edge) between terminal R
and terminal 15.
For the SIMODRIVE 611 universal HRS control unit, the reset is effective if, in
addition, terminal 65 "controller enable" is also inhibited.
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Type
Pull–in power [VA]
50 Hz
60 Hz
3TK48
330
378
3TK50
550
627
For 50 Hz line supplies
4AM4096–0EM50–0AA0
80
380/230
415 (min. 360/max. 458)
0.193
T40/B
EN 61558–13
50/60
IA0
IP00
PD10 T8/2
+10% –13.2 %
© Siemens AG 2012 All Rights Reserved
11.05
05.01
Holding power [VA]
50 Hz
60 Hz
36
44.2
32
39
For 60 Hz line supplies
4AM4696–0EM70–0F A0
80
380/230
460/415
0.19...0.17
T40/B
VDE 0532
50/60
Ii0
IP00
LV 10
+10% –13.2 %