Siemens SIMEAS R-PMU Manual page 272

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

18
18.3 Recording Functions
Continuous mean value recorder for frequencies
Recording procedure: continuously
Averaging time: 1 s, 2 s, 5 s, 10 s, 30 s, 60 s, 120 s, 240 s, 300 s, 360 s, 480 s, 600 s
Table 18-17
VCDAU
f
Continuous mean value recorder for fundamental component rms values of current and voltage
Recording procedure: continuously
Averaging time: 1 s, 2 s, 5 s, 10 s, 30 s, 60 s, 120 s, 240 s, 300 s, 360 s, 480 s, 600 s
Table 18-18
VCDAU
V
, V
, V
L
N
V
, V
, V
1
2
I
, I
, I
L
N
I
, I
, I
1
2
0
Continuous mean value recorder for active and reactive power
Recording procedure: continuously
Averaging time: 1 s, 2 s, 5 s, 10 s, 30 s, 60 s, 120 s, 240 s, 300 s, 360 s, 480 s, 600 s
Table 18-19
VCDAU
P
, Q
Σ
Continuous mean value recorder for process values
Recording procedure: continuously
Averaging time: 1 s, 2 s, 5 s, 10 s, 30 s, 60 s, 120 s, 240 s, 300 s, 360 s, 480 s, 600 s
Usable DAU: DDAU
Recorded values: process values D
Event recorder (ER)
Recording of state changes of the binary signals (1 data set per binary change)
Sampling values: 1 kHz resolution, 250 state changes per second
Accuracy of the time stamping of recorded state changes: 1 ms
272
Recorded values of the DAUs
VDAU
f
Recorded values of the DAUs
VDAU
V
, V
, V
L
N
V
, V
, V
0
1
2
0
Recorded values of the DAUs
coupled CDAU
, P, Q
Σ
CDAU
f
CDAU
I
, I
, I
L
N
I
, I
, I
1
2
0
P
, Q
, P, Q
Σ
Σ