Siemens SIMEAS R-PMU Manual page 158

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

12
12.11 Slot Description
VCDAU and coupled CDAU at star and delta connection
PSUM1-3
PSUM5-7
P4
P8
QSUM1-3
QSUM5-7
Q4
Q8
FREQ1
FREQ2
Total powers are calculated from the first 3 channels of a group.
VDAU and not coupled CDAU
FREQ1
FREQ2
Select one calculated values from the drop-down menu of the Channel box.
Enter the Channel Description and Abbreviation and select a Color.
Select under Display in OSCOP P whether the values of the channel are to be displayed in
the OSCOP P Evaluate module.
Use the Display range min and Display range max boxes to set the lowest or highest
respectively measured value to be displayed in the OSCOP P Evaluate module. Select the
measured value dimension.
Note
Digits following the points are regarded as decimal places.
Set the value for the zero crossing in the Time axis position box for evaluating the measured
values in the OSCOP P Evaluate module. Negative values are allowed.
158
Total active power group 1 of the coupled CDAU
Total active power of VCDAU and group 2 of the coupled
CDAU
Active power of channel 4 group 1 of the coupled CDAU
Active power of channel 4 of VCDAU and group 2 of the
coupled CDAU
Total reactive power group 1 of the coupled CDAU
Total reactive power of VCDAU and group 2 of the coupled
CDAU
Reactive power of channel 4 group 1 of the coupled CDAU
Reactive power of channel 4 of VCDAU and group 2 of the
coupled CDAU
Frequency calculated using the best signal of the first
measured value recording group (channels 1 to 4) of the DAU
Frequency calculated using the best signal of the second
measured value recording group (channels 5 to 8) of the DAU
Frequency calculated using the best signal of the first
measured value recording group (channels 1 to 4) of the DAU
Frequency calculated using the best signal of the second
measured value recording group (channels 5 to 8) of the DAU