18.1 Modules of the SIMEAS R-PMU

18.1
Modules of the SIMEAS R-PMU
Interaction between the modules
Figure 18-1 Device architecture, internal / external communication and power supply
Functions of the modules
CPU: Control of all device-internal processes, the communication with external devices and
the data processing
DAUs: Measured value acquisition and processing of measured values in lines connected to
the DAUs
Power supply unit and battery package (option): Infeed of the supply voltage, distribution in
the SIMEAS R-PMU and optional uninterruptible power supply
External communication interfaces
LAN (rear panel): Network connection (LAN) for the data transmission between SIMEAS R-
PMU and evaluation PC, DAKON or PDC
COM 1 (rear panel): Serial interface for the transmission of parameters and measured data
between SIMEAS R-PMU and evaluation PC, DAKON or PDC
via direct coupling
via external analog modem / ISDN modem
via FO converter and star coupler if several devices are connected (no connection to
PDC possible)
via X.25 communication (no connection to PDC possible)
COM S (front panel): Serial service interface for the parameterization and transmission of
measured data from the SIMEAS R-PMU to the evaluation PC or DAKON
LPT 1 (rear panel): Parallel printer interface
7B1(+), 7B2(-) (rear panel): Connection for the GPS timer for synchronization
Binary and relay outputs (rear panel)
262
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012