Mitsubishi Electric MELSEC-Q Structured Programming Manual page 141

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]
Number and name
Clock
[M]8010
Unavailable
Turns ON and OFF in 10 ms cycle (ON duration: 5 ms, OFF
[M]8011
duration: 5 ms).
10 ms clock
Turns ON and OFF in 100 ms cycle (ON duration: 50 ms,
[M]8012
OFF duration: 50 ms).
100ms clock
Turns ON and OFF in 1 sec cycle (ON duration: 500 ms,
[M]8013
OFF duration: 500 ms).
1 sec clock
Turns ON and OFF in 1 min cycle (ON duration: 30 s, OFF
[M]8014
duration: 30 s).
1 min clock
Stops and presets time counting.
M 8015
For real-time clock
Stops the time display.
M 8016
For real-time clock
Corrects by ±30 seconds.
M 8017
For real-time clock
Detects installation (Always remains ON).
[M]8018
For real-time clock
Notifies a real-time clock (RTC) error.
M 8019
For real-time clock
Flag
[M]8020
Turns ON when the addition or subtraction result is "0".
Zero
[M]8021
Turns ON when the subtraction result is less than the
Borrow
maximum negative value.
M 8022
Turns ON when "carry" occurs in the addition result, or when
Carry
overflow occurs in the shift operation result.
[M]8023
Unavailable
*1
Specifies the BMOV instruction execution direction.
M 8024
*1
Indicates the HSC mode.
M 8025
*1
Indicates the RAMP mode.
M 8026
*1
Indicates the PR mode.
M 8027
Changes over the 100 ms timer and 10 ms timer.
M 8028
Enables interrupts while the FROM/TO instruction is
executed.
[M]8029
Instruction execution
Turns ON when the operation of DSW, etc. is completed.
complete
*1.
Cleared when the PLC mode switches from RUN to STOP.
4 Operations of Special Devices (M8000 and later, D8000 and later)
Operation and function
→ Refer to Subsection 4.2.6.
→ Refer to Subsection 4.2.6.
→ Refer to Subsection 4.2.6.
→ Refer to Subsection 4.2.6.
→ Refer to Subsection 4.2.7.
→ Refer to Subsection 4.2.7.
→ Refer to Subsection 4.2.7.
→ Refer to Subsection 4.2.7.
→ Refer to Subsection 4.2.7.
4.1 Special Device List (M8000 and later, D8000 and later)
Applicable model
FX
FX
FX
FX
3U
3UC
3G
3GC
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Corresponding
FX
3S
special device
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
139
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-lMelsec-fFx3sFx3gFx3gcFx3u ... Show all

Table of Contents