Huawei NetCol5000-C030 User Manual page 33

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Table 2-2 Pipe ports
Item
Water outlet
pipe
Water inlet pipe
(Optional)
Humidifier water
inlet pipe
Drainpipe
Installation Requirements
Table 2-3 Installation requirements
Item
Room
door
Floor
Pipe
routing
Cabling
mode
Drainage
requirem
ents
Issue 04 (2021-03-15)
NetCol5000-C065
G 1–1/2 inch internal thread
connector
G 1–1/2 inch internal thread
connector
G 3/4 inch external thread
connector
BSPP 1/2 inch internal thread
connector
NetCol5000-C065
2 m high cabinet: width ≥ 1.2
m, height ≥ 2.3 m. The
cabinet may topple over in a
short time.
Raised floor bearing capacity ≥ 530 kg/m
Raised floor height ≥ 250 mm
NOTE
If pipes are routed from the top, there is no requirement on the height of the
raised floor.
Bottom pipe routing or top and bottom pipe routing
Top cabling
Automatic drainage or forcible drainage
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-C030/C032
G 1 inch internal thread
connector
G 1 inch internal thread
connector
G 3/4 inch external thread
connector
BSPP 1/2 inch internal
thread connector
NetCol5000-C030/C032
● 2 m high cabinet: width ≥ 1.2 m,
height ≥ 2.3 m. The cabinet may
topple over in a short time.
● 2.2 m high cabinet: width ≥ 1.2
m, height ≥ 2.5 m. The cabinet
may topple over in a short time.
2
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents