NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
●
●
Parameters of System Control
●
●
●
4.6 Startup and Wizard Startup
4.6.1 First Startup Flowchart
Offline Boot or Online Boot can be selected for the first startup.
● Download the Service Expert app from HUAWEI AppGallery. The app can only
run on Android currently. You must apply for the permission to use the app
after downloading it.
● Indoor fan commissioning is a mandatory item for power-on commissioning.
Other components can be commissioned depending on actual requirements.
● If this is not the first startup, choose Maint > Wizard Startup to enter the
wizard startup mode.
● If no humidifier is configured, its commissioning item is not displayed.
Issue 04 (2021-03-15)
When Indoor fan control type is set to Pressure diff ctrl, Air-side difference
pressure sensor type can not be set to No or 0~500Pa.
When Indoor fan control type is not set to Pressure diff ctrl, Air-side
difference pressure sensor type cannot be set to 0~500Pa.
Cooling start temperature demand > Cooling stop temperature demand
Lower limit for dehumid start temperature demand > Lower limit for dehumid
close temperature demand
Upper limit for dehumid start temperature demand > Upper limit for dehumid
close temperature demand
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
111