FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Figure 4-80 Securing the fastening plates
Step 7 Switch on the standby power supply to the fire alarm control panel.
Step 8 Check that the new batteries are working properly.
If the BATTERY FAULT indicator on the fire alarm control panel is off, the batteries are working
properly.
----End
Follow-up Procedure
Dispose of the removed fire alarm control panel batteries that are confirmed
faulty.
4.4.11 Replacing a Fire Cylinder
Prerequisites
A spare fire cylinder of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Prerequisites
Tools: pallet truck, Phillips screwdriver, protective gloves, adjustable wrench
Materials: spare fire cylinder, sealing tape
Document: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Issue 01 (2021-04-20)
NO TE
Copyright © Huawei Technologies Co., Ltd.
4 Parts Replacement
135