FusionModule500 Smart Mini Data Center
User Manual
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 5-19 IP parameters
Path
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
Step 3 Click Submit.
Step 4 Set the NetEco communication parameters and authentication password on the
ECC800-Pro WebUI.
Table 5-20 NetEco parameters
Path
System
Settings >
NMS
Application
> NetEco >
Communicat
ion
Parameters
Issue 01 (2020-11-30)
Parameter
Default
Value
IP address
192.168.8.1
0
Subnet
255.255.25
mask
5.0
Default
192.168.8.1
gateway
Parameter
NetEco
Location
Server IP
Port number
Copyright © Huawei Technologies Co., Ltd.
Setting
Set this parameter based on the IP
address assigned by the network
administrator.
Set this parameter based on the
subnet mask assigned by the network
administrator.
Set this parameter based on the
default gateway address assigned by
the network administrator.
Default
Setting
Value
Local
Set this parameter based on the
type of the connected NetEco
management system.
Local: NetEco
Cloud: CloudOpera NetEco
192.168.8.
IP address of the primary NetEco
11
server
NOTE
The NetEco IP address and the ECC800-
Pro IP address must be configured in
the same network to ensure normal
connection between the NetEco and
the ECC800-Pro.
31220
31220
5 Power-On Commissioning
161