GE FVP110 Maintenance Manual page 36

Table of Contents

Advertisement

GE Energy
Note1
Model FVP110 Advanced Valve positioner with optional code /KS25 for potentially
explosive atmospheres: No. KEMA 02ATEX1274X
Applicable standard: EN50014, EN50020, EN500284, EN50281-1-1
Certificate: KEMA 02ATEX1274X
Note 2. Ratings
[EEx ia IIC T4]
Type of Protection: EEx ia IIC T4
Group: 1G, 1D, 1GD
Maximum Surface Temperature for dust proof.: T100 °C
Ambient Temperature for 1G: -40 °C to + 60 °C
Ambient Temperature for 1GD: -40 °C to + 60 °C
Degree of Protection of the Enclosure: IP65
Electrical Data
When combined with Entity model IIC barrier
Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Cint = 1.76 nF, Lint = 0 μH
When combined with Trapezoidal or Rectangular output characteristic FISCO model IIC
barrier
Ui = 17.5 V, Ii = 360 mA, Pi = 2.52W,
Cint = 1.76 nF, Lint = 0ìH
[EEx ia IIB T4]
Type of Protection: EEx ia IIB T4
Group: 1G, 1D, 1GD
Maximum Surface Temperature for dust proof.: T100 °C
Ambient Temperature for 1G: -40 °C to + 60 °C
Ambient Temperature for 1GD: -40 °C to + 60 °C
Degree of Protection of the Enclosure: IP65
Electrical Data
FVP 110 Fieldbus Valve Positioner Manual