Parameters of Resource Block
Relative
Index
Parameter
Index
37
1037
ALARM_SUM Enable
38
1038
ACK_
OPTION
39
1039
WRITE_PRI
40
1040
WRITE_ALM
41
1041
ITK_VER
42
1042
SOFT_REV
43
1043
SOFT_DSC
44
1044
SIM_ENABLE
_MSG
45
1045
DEVICE_STA
TUS_1
46
1046
DEVICE_STA
TUS_2
47
1047
DEVICE_STA
TUS_3
48
1048
DEVICE_STA
TUS_4
49
1049
DEVICE_STA
TUS_5
50
1050
DEVICE_STA
TUS_6
Table 60 Resource Block Parameters (Continued)
Default
Name
(factory
setting)
0XFFFF
0
—
4
—
—
Null
0
0
0
0
0
0
Write
Shows the alarm summary for all blocks within
the device (FVP110).
Defines the acknowledgment action of each
alarm type.
By setting a bit to 1, the corresponding alarm
will behave as acknowledged immediately
when it occurs without receipt of
acknowledgment from the host.
Defines the priority level of WRITE_ALM as
well as allows for notification to be disabled
and makes acknowledgment unnecessary for
WRITE_ALM.
—
Alarm generated when WRITE_LOCK is set to
unlocked
—
Version number of the inter-operability test kit
—
Revision number of software
—
Revision number of software for development
purpose.
—
Used to determine whether to enable the
simulation function to run. To enable, set
"REMOTE LOOP TEST SWITCH".
—
Shows device statuses - mainly link object
setting statuses.
—
Shows device statuses - mainly individual for
each block status.
—
Shows device statuses - mainly the contents of
XD_ERROR in each block.
—
Not used in the FVP110.
—
Not used in the FVP110.
—
Not used in the FVP110.
187
Function Block Parameters
Description