Parameters of Transducer Block
Relative
Index
Parameter
Index
33
2033
POSITION_
CHAR
_TYPE
34
2034
POSITION_
CHAR
35
2035
LIMSW_HI_
LIM
36
2036
LIMSW_LO_
LIM
37
2037
ELECT_
TEMP
38
2038
TEMPERATU
RE
_UNIT
39
2039
SUPPLY
_PRESSURE
40
2040
SPRING_
RANGE
41
2041
OUT_
PRESSURE
Table 61 Transducer Block Parameters (Continued)
Default
Name
(factory
setting)
1
10,20,30,40,5
0,60,
70,80,90
+110%
-10%
1101(°C)
140 kPa
20 kPa, 100
kPa
Write
O/S
Defines the valve position-to-flow
characteristics:
1 = linear
2 = equal % (50:1)
3 = equal % (30:1)
4 = quick open (inverse of 50:1 equal %)
5 = Camflex Percentage
255 = user-defined 10-segment function
O/S
Defines the coordinates of the segment
function when 255 is set for
POSITION_CHAR_TYPE.
[0 to 100, only simple decreasing can be
allowed]
Setting of high limit switch
Setting of low limit switch
Indicates the temperature on amplifier board
O/S
Defines the unit of temperature indication
above:
1101 = °C
1102 = °F
O/S
Air supply pressure (irrespective of control)
O/S
Defines the pressure range and unit for valve
operation (with no direct effect on control). The
unit defined here also applies to
OUT_PRESSURE.
1133 = kPa
1137 = bar
1141 = psi
1145 = kgf/cm
Output pressure to valve actuator
191