Bosch CL300 Manual page 96

Hide thumbs Also See for CL300:
Table of Contents

Advertisement

System Modules
4.4
Output Modules
All specifications for output modules are referenced to operation with a fan unit.
4.4.1
Digital Output Modules
Function
Configuration
Connection
Specifications
4−44
Caution
The digital output modules convert the internal signal levels to the exter
nal process signals.
8−channel, 16−channel, and 32−channel output modules are avail
able. The output circuits are electrically isolated from the internal logic
circuits through optocouplers and are overload protected by fuse links or
electronic circuit breakers. Each output has its own LED for indication of
the signal state.
LED off
−−> Logic 0"
LED on
−−> Logic 1"
All transducers are connected by plug−in terminals. This allows the re
placement of modules without removing the wire connections.
Cable Cross−section: 1.5 mm@ max.
Current Capacity of 1 Terminal: 6 A max. per contact
The following table lists the specifications of output modules.