Bosch CL300 Manual page 93

Hide thumbs Also See for CL300:
Table of Contents

Advertisement

Flexible Automation
Slot
A detailed description of the module is given in Technical Description" P .−No. 3913.
Specifications
Ordering Information
With the exception of expansion units in distributed expansion, the IE
module (interrupt mode) can be installed in any slot that accepts periph
eral modules.
. Note ,
External Supply Voltage
External Current Consumption
Internal Current Consumption
at 12 V
Voltage Range/Current Range
Signal Range 0"
Signal Range 1"
Number of Inputs
Switching Delay ON"
Switching Delay OFF"
Simultaneity Factor
Width
Dimensions
. Note ,
Shielded cable should be used for signal lines.
Interruptable Input Module IE 24 V
System Modules
24 V DC to DIN 19240
max. 100 mA
max. 30 mA
−3 V ... +5 V
0 ... 2.5 mA
+13 V ... +30.2 V
5.5 ... 13.5 mA
16
8 are switchable in interrupt
mode
10 ms typical
20 ms typical
100 %
1 module width
Dual Eurocard format
Order No.
050 564