9.3 Reference Scaling - Examples
9.3.1 Reference Scaling - Open Loop
Example:
par. F-52 Minimum Reference = 100 RPM
par. F-53 Maximum Reference = 1500 RPM
Reference send = 1500 hex (5376 dec)
Output:
The output can be calculated as:
F
Reference (decimal) ∗ (par.
− 53 − par.
16384
5376 * (1500 − 100)
+ 100 =
559 RPM
16384
F
− 52)
F
+ par.
− 52 =
AF-600 FP LonWorks
9
59