Reference [%]
Variable
SNVT
name:
type:
nviRefPcnt
SNVT_lev_percent
This variable sends the speed reference to the frequency converter. It represents a percentage of the reference range of the frequency converter.
In closed loop operation the reference is interpreted as the setpoint.
Reference [Hz]
Variable
SNVT
name:
type:
nviRefHz
SNVT_freq_hz
This variable sends the speed reference to the frequency converter in Hz, in open loop mode.
In closed loop mode it is used as the Set-point.
Closed Loop Set-point 1-3
Variable
SNVT
name:
type:
nviSetpoint1-3
SNVT_lev_percent
This variable sends up to 3 different set-points to the frequency converter via the bus.
NB!
Please refer to section Reference Handling for more information
Bus Feedback 1-3
Variable
SNVT
name:
type:
nviFeedback1-3
SNVT_lev_percent
This variable sends up to 3 different feedback signals to the frequency converter via the bus.
NB!
For more information on how to manage multiple set-points and feedback sources, please refer to AF-600 FP Programing Guide DET-620.
Value:
Min.
Max.
-163.840 %
+163.830 %
Value:
Min.:
Max.:
0.0 Hz
6,553.5 Hz
Value:
Min.:
Max.:
-163.840 %
163.830 %
Value:
Min.:
Max.:
-163.840 %
163.830 %
AF-600 FP LonWorks
Resolution:
0.005 %
5
Resulution:
0.1 Hz
Resulution:
0.005 %
Resulution:
0.005 %
19