5.7 Node Object

5.7.1 Node Object
5
5.7.2 Object Request
Variable name:
nviRequest
SNVT_obj_request
5.7.3 Object Response
Variable name:
SNVT type:
nvoStatus
SNVT_object_status
5.7.4 Max. Send Time (Heartbeat)
Variable
name:
nciMaxStsSendT
This variable configures a timer to send the nvoStatus object but only if bound to an input variable.
Maximum is '0 17:59:59:999' (0 days, 17 hours, 59 minutes, 59 seconds and 999 milliseconds).
Setting the timer to '0 0:0:0:0' disables it.
Network timer functions monitor node presence and control behavour in the event of network problems occurring.
34
SNVT type:
Supported functions:
RQ_Normal
RQ_Update_Status
RQ_Report_Mask
RQ_Disabled
RQ_Enable
This output network variable reports the status for any functional block on a device. It is also used to report the status
SNVT
type:
SNVT_elapsed_tm
These variables are used for controlling all functional blocks via the commis-
sioning tool.
Returns the specified functional block to normal operation.
Requests the status of the specified functional block.
Requests a status mask reporting the status bits that are supported by
the specified functional block.
Requests the specified functional block to change to the disabled state.
In the disabled state, output network variables belonging to the func-
tional block are not propagated within the network.
Requests the specified functional block to change to the enabled state.
In the enabled state, output network variables belonging to the func-
tional block are propagated within the network as defined by the func-
Description:
of the entire device and all functional blocks on the device.
Default value:
00:0:0:0
AF-600 FP LonWorks
Description:
tional block.
Min value:
Max value:
00:0:0:0
017:59:59:999