Chapter 4 Installation and Wiring
4.8 Wiring of the computer link
4
150
Cable connection examples show as below.
• Below figure shows an example of cable connection using the RS-232C/RS-485
converter (ADP-6237B).
• Use shielded twisted-pair cable for data communication suited to RS-485 standard.
The cable shield should be connected to single -point ground.
One to one configuration
Master
computer
TXD
RXD
RTS
CTS
SG
DTR
DSR
CD
RS-232C
(max.15m)
• On the S2, removable terminal block is provided for cable connection.
• Short between RXA and TERM for termination at both the S2 and the
ADP-6237B.
• If the master has RS-485 (or RS-422) interface and the CPU is connected to the
master directly, connect termination resistor 1/2 W - 120 Ω between RXA and RXB at
the master end.
RS-232C/RS-485 converter
(ADP-6237B)
3
RXD
TXA
2
TXD
TXB
5
CTS
RXA
4
RTS
RXB
7
SG
SG
6
DSR
TERM
20
DTR
FG
8
CD
1
FG
25-pin
Terminal
connector
block
model 2000 Sequence Controller S2 User's Manual -Basic Hardware-
S2
RXA
RXB
TXA
TXB
SG
TERM
RS-485
(max.1km)
Terminal
block