9.2.5.3

Enabling the local lock

• To enable the local lock, set parameter 16.04 to 2 (LOCKED).
With this parameter setting, local control (including the LOC-REM key)
is disabled.
If the CDP control panel or a DriveWindow PC is in local control mode
at the time that the local lock is enabled, they remain in local control
mode until they are switched to remote control mode. This means that
the CDP control panel displays the letter L until you press the
LOC-REM key.
9.2.5.3.1 Disabling the local lock
• To disable the local lock, set parameter 16.04 to 1 (OPEN).
With this parameter setting, switching between remote and local
control is enabled.
9.2.5.4

Remote control

In remote control mode, operational commands or reference values
usually come from a higher-level control system via fieldbus or
remote I/O.
However, with the following parameter settings it is possible to start and
stop the drive, to set the direction of rotation, and to enter reference
values from the CDP control panel.
• 11.01 EXT1 START/STOP/DIR = 10 (KEYPAD) or
12.03 EXT REF1 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
• 11.02 EXT2 START/STOP/DIR 10 (KEYPAD) or
12.06 EXT REF2 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)
• To enter the remote control mode, press the LOC-REM key.
- A blank space indicates full remote control from a higher-level
control system.
- The letter R indicates partial remote control (some commands
are enabled locally).
3BHS799208 E01 REV E
ACT
PAR
FUNC
DRIVE
I
0
ACS5000 WATER-COOLED USER MANUAL
1
600.0 rpm
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
09 CDP CONTROL PANEL
0
157/186