Preparing Cables For Cable Entries With Sealing Modules - ABB ACS5000 User Manual

Water-cooled
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

6.7.1.3

Preparing cables for cable entries with sealing modules

• Prepare cables with an outer cable screen or shield for EMC bonding
with the metal enclosure of the cabinet as illustrated.
1
2
3
4
5
6
(1) Sealing module
(2) Frame
(3) Conductive foil of sealing module
(4) Cable clamp
(5) Shrinkable sheath seal
(6) Heat-shrinkable termination
(7) Outer cable sheath
• Install the sealing modules according to the instructions of the
sealing module supplier.
3BHS799208 E01 REV E
Figure 6-14 Preparing power cables for sealing modules
ACS5000 WATER-COOLED USER MANUAL
7
8
12
9
10
11
(8) Cable sheath removed to expose
cable shield
(9) Shield extension to be connected
to PG busbar
(10) Cable screen extension to be
connected to the PG busbar
(11) Cable lug as specified by the cable
supplier and suitable for M12 bolt
(12) Sheath seal
06 ELECTRICAL INSTALLATION
107/186

Hide quick links:

Advertisement

Table of Contents
loading