Huawei NetCol5000-A User Manual page 79

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual
Menu
Home
Screen >
Settings >
System
Settings >
CW Valve
Issue 02 (2016-11-30)
Parameter
Description
conditioner will automatically
shield the low pressure
protection, which will be
deemed as normal by default
during the low pressure shield
period.
Hot gas bypass
Indicates the maximum liquid
valve max start
pipe temperature to start the
temp
hot gas bypass valve.
Hot gas bypass
Indicates the minimum liquid
valve min start
pipe temperature to start the
temp
hot gas bypass valve.
Hot gas bypass
Sets the minimum runtime
valve min on/off
time for the hot gas bypass
time
before it can be shut down, or
the minimum stop time before
it can be started.
Max adjust step
Sets the maximum step for
adjusting the chilled water
valve. You are not
recommended to change the
value.
Min valve
Sets the minimum openness of
opening for
the chilled water valve after
dehumid
entering the dehumidification
mode. You are not
recommended to change the
value.
Anti-cond valve
Sets the decrease of the
regu ratio
openness of the chilled water
valve after the
anti-condensation openness
protection is generated.
Temp diff at no
When the difference between
cooling
the current temperature and
temperature set point is greater
than the value, a No cooling
output alarm will be
generated, and the system will
be shut down. You are not
recommended to change the
value.
Supply water
N/A
temp sensor
Return water
N/A
temp sensor
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Parameter Description
Default Value
55.0° C
28.0° C
120s
50.0%
40.0%
5%
3.0° C
Disable
Disable
73