Huawei NetCol5000-A User Manual page 75

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual
Menu
Home
Screen >
Settings >
System
Settings >
Compresso
r
Issue 02 (2016-11-30)
Parameter
Description
recommended to change the
value.
Startup delay
Sets the delay time for starting
a compressor after startup
conditions are met.
Shortest runtime
Sets the minimum runtime for
shutting down the compressor
after it is started.
Shortest
Sets the minimum shutdown
shutdown time
for starting the compressor
after it is shut down.
Protection
Sets the delay time for
release delay
releasing the protection of
frequency rise or fall forbid
and for releasing the protection
of speed rise or fall forbid.
Min speed
Sets the minimum rotational
speed for the compressor.
Max speed
Sets the maximum rotational
speed for the compressor.
Min dehumid
Sets the minimum rotational
speed
speed for the compressor when
the precision air conditioner is
under dehumidification.
LF oil return
Sets the rotational speed for
speed
the precision air conditioner at
low frequency oil return.
HF oil return
Sets the rotational speed for
speed
the precision air conditioner at
high frequency oil return.
Oil return period
Sets the period of the precision
air conditioner for running at
oil return frequency.
Forced oil return
Sets the period allowed for the
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Parameter Description
Default Value
NetCol5000-A035
(025),
NetCol8000-A:
10s
NetCol5000-A020
: 26s
180s
NetCol5000-A020
: 150s
NetCol5000-A035
(025),
NetCol8000-A:
180s
60s
1500 RPM
NetCol5000-A025
: 4000 RPM
NetCol5000-A035
: 4500 RPM
3600 RPM
NetCol5000-A025
: 2700 RPM
NetCol5000-A035
: 3000 RPM
NetCol5000-A025
: 3300 RPM
NetCol5000-A035
: 3600 RPM
180s
NetCol5000-A020
69