Huawei NetCol5000-A User Manual page 70

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual
Menu
Issue 02 (2016-11-30)
Parameter
Description
Cooling off delay
Sets the time delay for cooling
when the ambient temperature
reaches the lowest temperature
based on the Temp set point.
Min dehumid
Sets the lower required
start temp
temperature limit for enabling
the dehumidification function.
Max dehumid
Sets the upper required
start temp
temperature limit for enabling
the dehumidification function.
Min dehumid
Sets the lower required
close temp
temperature limit for disabling
the dehumidification function.
Max dehumid
Sets the upper required
close temp
temperature limit for disabling
the dehumidification function.
Dehumid heat
Sets the upper required
start temp
temperature limit for starting
the electric heater during
dehumidification.
Low-temp heat
Sets the upper required
start temp
temperature limit for starting
the electric heater at low
temperature.
Max dehumid
Sets the dehumidification
runtime
duration for a precision air
conditioner in automatic mode.
Dew-point/sup-w
Sets the minimum temperature
ater TD for
difference between the
dehumid
ambient dew-point
temperature and supply water
temperature for enabling the
dehumanization.
Anti-cond
Sets whether to enable
protection
anti-condensation protection
(if disabled, no
anti-condensation protection
will be generated even when
protection conditions are met).
Anti-cond temp
When the supply air
diff
temperature is less than the
sum of the dew-point
temperature and Anti-cond
temp diff, the
anti-condensation protection
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Parameter Description
Default Value
180s
–10%
50%
–100%
100%
–50%
–100%
60 min
5.0° C
Enable
–2.0° C
64