ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
Code
(hex)
FF63
FF81
FF8E
Fault / Aux. code
0012
0013
STO diagnostics failure.
FB A force trip
EFB force trip
Cause
Motor too large for
Check that the motor and drive sizes
advanced standstill ID
are compatible.
run.
Contact your local ABB
representative.
(Asynchronous motors
Check that the motor nominal value
only)
settings in the drive are the same as
in the motor nameplate.
Motor data error.
Contact your local ABB
representative.
SW internal
Reboot the control unit (using
malfunction.
parameter 96.08 Control board boot)
or by cycling power.
A fault trip command
Check the fault information provided
has been received
by the PLC.
through fieldbus
adapter A.
A fault trip command
Check the fault information provided
has been received
by the PLC.
through the embedded
fieldbus interface.
ACH580 Ultra-Low Harmonic Drives Installation
73
What to do