Hydran 201Ci Controller Verification; Fuse - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Instruction Manual

14.8 Hydran 201Ci Controller Verification

Frequency: Annually or on fail alarm
Note: Alarms are triggered during this verification procedure. Please warn the
appropriate personnel.
The H201Ci is verified as follows:
1.
Check for water or dust infiltration inside the enclosure.
2.
If necessary, clean and fix the enclosure.
3.
Check for loose connections on the terminal blocks and connectors. Retighten if
necessary.
WARNING
4.
Verify the LED's, the heater and the display by performing the procedure in
Section 9.2.2.
5.
Verify the Hydran 201Ci-1's analog output by performing the procedure in Section
9.2.3.
6.
If the H201Ci-1 is not currently in operation and if its alarm contacts are used
(connected to a SCADA system), verify the alarm indicators and relays by
performing the procedure in Section 9.2.4.
7.
Verify the RS-232 or USB and RS-485 communications by performing the
procedure in Section 8.2.3.

14.9 Fuse

The Hydran 201Ti, the Hydran 201Ci-C and the Hydran 201Ci-1 require the following
type of fuse:
• 5 A
• 250 VAC
• 5 x 20mm
• Slow blow / Time delay
MA-033
Rev. 14.0, 12-Nov-18
AC power supply voltage is present on most terminals.
Page 199