Storage; Verification Of Operation Prior To Installation; Preparation - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Instruction Manual

9.1.3 Storage

If the Hydran 201Ci-1 is not installed immediately, it is strongly recommended to
store it in its original shipping box in a safe place. Ensure that the door-mounted push-
buttons are covered with the protective caps.
Storage should be at a temperature between 5 and 45°C (41 and 113°F) and a non-
condensing, relative humidity between 5 and 95%; if these limits are to be exceeded,
please contact the General Electric Customer Service (contact information can be found
at the bottom of page 2). These restrictions do not apply to transportation.
9.2

Verification of Operation Prior to Installation

It is strongly recommended that you verify the operation of the Hydran 201Ci-1
Controller before installation in the field. The verification confirms that no damage
occurred during shipping and allows the user to become familiar with the H201Ci-1.

9.2.1 Preparation

To verify its operation, the Hydran 201Ci-1 must first be connected to a functional
Hydran 201Ti via a supervisory link cable. One end of this cable is already connected to
the H201Ti. For details on commissioning the H201Ti(s), see Chapter 7.
Proceed as follows:
1. Connect a three-wire power cord to the AC Power 3-Terminal Block on the first
H201Ti (item 8 in Figure 3-4): The live side to L1/L, the other side to L2/N, and the
ground to E/G. For additional wiring details, see Table D - 1.
2. Connect the second end of the three-pair supervisory link cable coming out of the
H201Ti to the main terminal block on the H201Ci-C (item 6 in Figure 4-6).
3. Power On the H201Ti.
4. Ensure the H201Ti is operating normally and no gas or fail alarms are present, by
looking at the small LED indicators on the right side of the I/O module (refer to
Section 3.4.6.3).
5. Connect a power cord to the terminals 1 and 2 on the main terminal block of the
H201Ci-1 (item 6 in Figure 4-6) and connect the E/G wire to the enclosure chassis.
6. Power On the H201Ci-1.
MA-033
Rev. 14.0, 12-Nov-18
Page 131

Advertisement

Table of Contents
loading

Table of Contents