Motor-side power components
9.4 dv/dt filter compact plus Voltage Peak Limiter
NOTICE
Damage to the dV/dt filter compact if it is not activated during commissioning
The dV/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter compact during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dV/dt filter compact if a motor is not connected
dV/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a dV/dt filter compact connected to the Motor Module without a
Note
Cable lengths
Keep the connecting cables to the Motor Module as short as possible (max. 5 m). Use an
equivalent cable type when replacing the cables supplied.
392
connected motor.