Completing The Test; Event Function Event; Fault Locator Lmbrflo - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN E
10.1. Test the actual set value defined by
10.2. The output GPRESALM is activated after a time greater than set time of
10.3. The output GPRESLO is activated after a set time of
11.12.3.2

Completing the test

1.
Continue to test another function or end the test by changing the
Off .
2.
Restore connections and settings to their original values if they were changed for testing
purposes.
11.12.4

Event function EVENT

Prepare the IED for verification of settings as outlined in section
chapter.
During testing, the IED can be set when in test mode from PST. The functionality of the event
reporting during test mode is set in the Parameter Setting tool in PCM600.
Use event masks
Report no events
Report all events
In test mode, individual event blocks can be blocked from PCM600.
11.12.5

Fault locator LMBRFLO

Prepare the IED for verification of settings as outlined in section
section
The Fault locator function LMBRFLO depends on other functions to work properly, that is,
phase selection information from distance protection function and analog information
supplied by the trip value recorder function. Check that proper binary start and phase
selection signals are connected and voltage and current signals are configured (parameter
settings).
The result is displayed on the local HMI or via PCM600. Distances to faults for the last 100
recorded disturbances can be found on the local HMI under Main menu/Disturbance Records/
Disturbance #n(n = 1–100)/General Information
If PCM600 is used, the result is displayed on the recording list after upload, including loop
selection information.
Bay control REC670
Commissioning manual
tDGasPresAlm value if the input PRESALM is enabled.
PRESLO is enabled.
"Preparing for test"
in this chapter.
© Copyright 2017 ABB. All rights reserved
Testing functionality by secondary injection
tDGasPresAlm and tDGasPresLO .
tDGasPresLO value if the input
"Preparing for test"
"Requirements"
Section 11
GUID-0A16206F-690E-46EF-86F4-5A89E0BF640B v3
Test mode setting to
M11751-2 v5
in this
M14955-2 v7
and
177