5.4.2 Power Cable Specifications

YJV5 cables are recommended. When the ambient temperature is 40° C, the conductor
working temperature cannot exceed 90° C.
Table 5-7 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)

5.4.3 Preparing Terminals

Figure
end terminals.
Issue 02 (2017-02-24)
Cable Layout Rule
Connection ports and cabling methods facilitate maintenance, cable
routing, and capacity expansion.
Cable connectors prepared onsite must be normal, secure, reliable, and
neat.
Power cables, ground cables, and various signal cables are securely
connected. Adapters are securely plugged or screwed.
The N and PE cables are bound separately from the L1/L2/L3 or L cables
for each circuit breaker. Cables are converged at the beam and bound in
groups by cable ties.
Rated
Current
160 A
250 A
400 A
160 A
250 A
400 A
< 10 A
10 A ≤ I ≤ 40
A
< 10 A
10 A ≤ I ≤ 40
A
5-17,
Figure
5-18, and
Figure 5-19
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cable
Terminal/Bolt
Diameter
Specifications
2
50 mm
DT-M10
2
95 mm
DT-M12
2
185 mm
DT-M16
2
25 mm
DT-M10
2
50 mm
DT-M10
2
95 mm
DT-M12
2
Cord end terminal
2.5 mm
(plug depth 8–12
mm)
2
6 mm
Cord end terminal
(plug depth 8–12
mm)
2
2.5 mm
OT-M6
2
6 mm
OT-M6
respectively show how to prepare DT, OT, and cord
5 Installation Guide
Recommended
Torque
26–33 N· m
46–58 N· m
46–58 N· m
26–33 N· m
26–33 N· m
46–58 N· m
1.5–1.8 N· m
1.5–1.8 N· m
4.9 N· m
4.9 N· m
46