PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Figure 5-14 Not tied at bends
Figure 5-15 Extra length for easier plug and unplug
Figure 5-16 Stroking cables
Cable Layout
Table 5-6 Cable layout rules
No.
1
2
3
4
5
Issue 02 (2017-02-24)
Cable Layout Rule
The armoring layers of armored cables are grounded.
The PDC ground cable is secured to the equipment room ground bar. Use
a multimeter to measure the resistance between the PDC ground cable and
the equipment room ground bar, and verify that the reading is less than 0.1
ohm.
Cables are securely connected in the correct phase sequence.
Cables are neatly arranged, and cable insulation layers are intact.
Different types of cables are bound separately.