PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Figure 7-107 DIP switches
The following lists the functions of the DIP switches:
To clear historical records and logs, you must log in as the admin user.
Table 7-3 Functions of the DIP switches
Function
Clear
historical
alarms.
Clear logs.
Restore
factory
settings.
Issue 02 (2017-02-24)
DIP1: Controls the CAN build-out resistor and is set to ON by default.
DIP2 to DIP4: Work together with specified buttons to clear historical records and logs
and restore factory settings.
Status
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
DIP2
DIP3
DIP4
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
7 MDU Commissioning Guide
Button
Action
Operation
Press and
Clear
hold Active
historical
Alarm for
alarms.
about 10s.
Press and
Clear
hold
operation
logs
Buzzer Off
for about
(APP/LUI).
10s.
The MDU
automatically
restarts
during the
process.
Press and
The MDU
hold
automatically
Buzzer Off
restarts after
for about
factory
10s.
settings are
restored.
122