Commissioning
6.2 Commissioning TM54F by means of STARTER/SCOUT
● F-DI selection (p10006)
● Function mode selection (in preparation)
6.2.4

F-DI/F-DO configuration

Inputs screen F-DI
Figure 6-3
NC/NO contact (p10040)
Terminal property F-DI 0-9 (p10040.0 = F-DI 0, ... p10040.9 = F-DI 9). Configure only the
property of the second (lower) digital input. Always connect an NC contact to digital input 1
(upper). Digital input 2 can be configured as NO contact.
74
detection (e.g. switch the L1+ and L2+ sensor power supply). Each selection triggers a
timer in order to monitor the test cycle. An alarm is set on expiration of the monitored
time.
The Extended Functions enter a safety alarm in a special alarm buffer upon the detection
of internal errors or violation of limits. This alarm must be acknowledged safely. You can
assign an F-DI terminal pair for safe acknowledgment.
Inputs screen
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0
Safety Integrated