Overview Of The F-Dis - Siemens SINAMICS S120 Function Manual

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control of the safety functions
5.3 Control by way of TM54F terminals
5.3.2

Overview of the F-DIs

Description
Failsafe digital inputs (F-DI) consist of two digital inputs. The cathode of the optocoupler is
routed to the second digital input in order to allow the connection of an M-switching F-DO
output (the anode must be wired to 24 V DC).
Parameter p10040 is used to determine whether an F-DI is operated as NC/NC or NC/NO
contact. The status of DI can be read at parameter r10051 for the drive objects TM54F_MA
and TM54F_SL. The same bits of both drive objects are logically linked by AND operation
and return the status of the relevant F-DI.
The signal states at the two associated digital inputs (F-DI) must assume the same status
configured in p10040 within the monitoring time set in p10002.
IN order to enable forced dormant error detection, connect the digital inputs of F-DI 0 ... 4
with the dynamic voltage supply L1+ and the digital inputs with F-DI 5 ... 9 to L2+ (for
additional information on forced dormant error detection, refer to the corresponding function
description in the chapter "Extended Functions").
X521.1
X521.2
X521.3
X521.6
X521.4
X521.5
X521.7
X521.8
X522.1
X522.2
X522.7
X522.3
X522.4
X522.8
X522.5
X522.6
X522.9
X522.10
Figure 5-3
Overview of F-DI 0 ... 4
62
L1+
DI 0
p10040.0
M1
DI 1+
0
DI 1-
1
1
DI 2
p10040.1
M1
DI 3+
0
DI 3-
1
1
M1
DI 4
p10040.2
M1
DI 5+
0
DI 5-
1
1
DI 6
p10040.3
M1
DI 7+
0
DI 7-
1
1
DI 8
p10040.4
M1
DI 9+
0
DI 9-
1
1
M1
p10002
T
r10051.0 (SL)
=1
r10051.0 (MA)
T
r10051.1 (SL)
=1
r10051.1 (MA)
T
=1
r10051.2 (SL)
r10051.2 (MA)
T
r10051.3 (SL)
=1
r10051.3 (MA)
T
r10051.4 (SL)
=1
r10051.4 (MA)
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0
0
F35151
F-DI 0
&
0
F35151
F-DI 1
&
0
F35151
F-DI 2
&
0
F35151
F-DI 3
&
0
F35151
F-DI 4
&
Safety Integrated