Table 4-1
F-DI for bit 0 (r9720.9)
0
0
1
1
The changeover from a lower to a higher speed limit takes effect without any delay.
The changeover from a higher to a lower limit triggers a delay time which can be set at the
corresponding parameter (p9351 and p9551).
In order to reach the reduced speed that is below the new limit value, the drive must be
decelerated accordingly within the delay time. However, if the actual speed is higher than the
new limit value and the time has expired, an appropriate alarm with the configured stop
response will be generated.
Overview of important parameters (refer to the List Manual)
● p9301.0 SI motion enable safety functions (Motor Module), enable SOD/SLS
● p9501.0 SI motion enable safety functions, enable SOS/SLS
● p9331 SI motion SLS limits (Motor Module)
● p9531 SI motion SLS(SG) limits (Control Unit)
● p9533 SI motion speed setpoint limit (Control Unit)
● p9351 SI motion SLS changeover delay time (Motor Module)
● p9551 SI motion SLS changeover delay time (Control Unit)
● p9363 SI motion stop response SLS (Motor Module)
● p9563 SI motion SLS(SG)-specific stop response (Control Unit)
● r9720 CO/BO: SI motion integrated drive control signals
● r9722 CO/BO: SI motion integrated drive status signals
● r9733 CO: SI motion effective speed setpoint limiting
Safety Integrated
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0
Changeover of speed limits:
F-DI for bit 1 (r9729.10)
0
1
0
1
Extended Functions
4.4 Safely Limited Speed (SLS)
Speed limit
p9331[0]/p9531[0]
p9331[1]/p9531[1]
p9331[2]/p9531[2]
p9331[3]/p9531[3]